![]() 07/27/2018 at 12:11 • Filed to: None | ![]() | ![]() |
My friend has a service panel where neutral and ground share one bus. Will a GFI outlet function properly
in that situation?
![]() 07/27/2018 at 12:19 |
|
NFI
![]() 07/27/2018 at 12:23 |
|
NSFW.
![]() 07/27/2018 at 12:31 |
|
Generally the neutral bus and ground bus should be separate. I would imagine a GFI would fault out in this instance. So in this case I think they are using the ground bus as the neutral bus? How does that even work? I think a call to a professional electrician is in order.
![]() 07/27/2018 at 12:32 |
|
Yes. In most situations, the ground and neutral buses are bonded together, and in many they are physically the same bus . As long as the outlet is wired according to instructions (especially if there are to be downstream outlets protected by that GFI outlet) it will be just fine.
![]() 07/27/2018 at 12:36 |
|
Actually, neutral needs to be tied to ground somewhere for electricity to work. It is done in the main service panel where electricity comes into the house ONLY. A good practice would still be to keep two separate bars for ground and neutral and then tie them together, but since they are all right there a lot of times you’ll find everything on one bar in the main panel. Any sub panels must have two separate bars.
![]() 07/27/2018 at 12:40 |
|
I’m not an electrician, but assuming this is the main service panel for the building there is no problem. The ground and neutral will always be tied together there. In this case someone was lazy and put it all on one bar instead of tying together separate ground and neutral bars. So the GFCI’s downstream should be fine. If this isn’t the main panel, have your friend call in a pro before he hurts himself.
![]() 07/27/2018 at 12:42 |
|
That’s a good explanation
, I did some more research and figured that out too. My house is very strange it has one main panel
and three sub panels so everything is not normal.
![]() 07/27/2018 at 12:46 |
|
Also... that wire loop... those are usually used for hooking on an ammeter which could mean someone was trying to sleuth out a ground fault in the past. It could be nothing or it could be a preemptive thing put in for future maintenance but it could also mean past issues. Personally I’d at least consult a pro over that.
![]() 07/27/2018 at 13:10 |
|
Is the service panel in an older (pre-60s) house? It used to be pretty standard to tie N and G together- many older houses didn’t even have a ground terminal on outlets.
It’s probably fine if it’s in a house, but if there are significant jumps in load (like a large heater on the circuit or something), the potential on the neutral will briefly be not at ground potential, which would present a hazard. May also trip the interrupt.
If it’s in a non-residential application, the wiring probably isn’t up to code and should be fixed. In either case, it’s probably worth getting an electrician out there to isolate N and G.
![]() 07/27/2018 at 13:46 |
|
I’m not entirely sure how that affects the GFCI stuff, but last year a technician who came to look at the furnace was a worried about potential backfeeding , and needed the grounds separated from the neutrals before he could complete his diagnosis.
So I had to rewire the main panel with a dedicated ground circuit. There was already a grounding rod nearby, so it wasn’t all that hard, just time consuming. Especially because all the wires were left long and just stuffed in there. Here you can see the tangled mess on the left-hand side, compared with the ones on the right that I trimmed and rewired. It’s so much easier to trace wires now, should the need ever arise.
!!!error: Indecipherable SUB-paragraph formatting!!!